Class Description

Frequency and active power controller model.
Reference: IEC 61400-27-1:2015, Annex D.

Attributes

Name Type Description
dprefmax PU Maximum ramp rate of pWTref request from the plant controller to the wind turbines (dprefmax) (> WindPlantFreqPcontrolIEC.dprefmin). It is a case-dependent parameter.
dprefmin PU Minimum (negative) ramp rate of pWTref request from the plant controller to the wind turbines (dprefmin) (< WindPlantFreqPcontrolIEC.dprefmax). It is a project-dependent parameter.
dpwprefmax PU Maximum positive ramp rate for wind plant power reference (dpWPrefmax) (> WindPlantFreqPcontrolIEC.dpwprefmin). It is a project-dependent parameter.
dpwprefmin PU Maximum negative ramp rate for wind plant power reference (dpWPrefmin) (< WindPlantFreqPcontrolIEC.dpwprefmax). It is a project-dependent parameter.
kiwpp Float Plant P controller integral gain (KIWPp). It is a project-dependent parameter.
kiwppmax PU Maximum PI integrator term (KIWPpmax) (> WindPlantFreqPcontrolIEC.kiwppmin). It is a project-dependent parameter.
kiwppmin PU Minimum PI integrator term (KIWPpmin) (< WindPlantFreqPcontrolIEC.kiwppmax). It is a project-dependent parameter.
kpwpp Float Plant P controller proportional gain (KPWPp). It is a project-dependent parameter.
kwppref PU Power reference gain (KWPpref). It is a project-dependent parameter.
prefmax PU Maximum pWTref request from the plant controller to the wind turbines (prefmax) (> WindPlantFreqPcontrolIEC.prefmin). It is a project-dependent parameter.
prefmin PU Minimum pWTref request from the plant controller to the wind turbines (prefmin) (< WindPlantFreqPcontrolIEC.prefmax). It is a project-dependent parameter.
tpft Seconds Lead time constant in reference value transfer function (Tpft) (>= 0). It is a project-dependent parameter.
tpfv Seconds Lag time constant in reference value transfer function (Tpfv) (>= 0). It is a project-dependent parameter.
twpffiltp Seconds Filter time constant for frequency measurement (TWPffiltp) (>= 0). It is a project-dependent parameter.
twppfiltp Seconds Filter time constant for active power measurement (TWPpfiltp) (>= 0). It is a project-dependent parameter.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

Source Class Cardinality Source Target Class Cardinality Target Source Name Source Assoc. Description Target Name Target Assoc. Description
WindPlantFreqPcontrolIEC 1 WindPlantIEC 1 WindPlantFreqPcontrolIEC Wind plant frequency and active power control model associated with this wind plant. WindPlantIEC Wind plant model with which this wind plant frequency and active power control is associated.
WindDynamicsLookupTable 1..* WindPlantFreqPcontrolIEC 0..1 WindDynamicsLookupTable The wind dynamics lookup table associated with this frequency and active power wind plant model. WindPlantFreqPcontrolIEC The frequency and active power wind plant control model with which this wind dynamics lookup table is associated.