Class Description

Q control model.
Reference: IEC 61400-27-1:2015, 5.6.5.7.

Attributes

Name Type Description
iqh1 PU Maximum reactive current injection during dip (iqh1). It is a type-dependent parameter.
iqmax PU Maximum reactive current injection (iqmax) (> WindContQIEC.iqmin). It is a type-dependent parameter.
iqmin PU Minimum reactive current injection (iqmin) (< WindContQIEC.iqmax). It is a type-dependent parameter.
iqpost PU Post fault reactive current injection (iqpost). It is a project-dependent parameter.
kiq PU Reactive power PI controller integration gain (KI,q). It is a type-dependent parameter.
kiu PU Voltage PI controller integration gain (KI,u). It is a type-dependent parameter.
kpq PU Reactive power PI controller proportional gain (KP,q). It is a type-dependent parameter.
kpu PU Voltage PI controller proportional gain (KP,u). It is a type-dependent parameter.
kqv PU Voltage scaling factor for UVRT current (Kqv). It is a project-dependent parameter.
rdroop PU Resistive component of voltage drop impedance (rdroop) (>= 0). It is a project-dependent parameter.
tpfiltq Seconds Power measurement filter time constant (Tpfiltq) (>= 0). It is a type-dependent parameter.
tpost Seconds Length of time period where post fault reactive power is injected (Tpost) (>= 0). It is a project-dependent parameter.
tqord Seconds Time constant in reactive power order lag (Tqord) (>= 0). It is a type-dependent parameter.
tufiltq Seconds Voltage measurement filter time constant (Tufiltq) (>= 0). It is a type-dependent parameter.
udb1 PU Voltage deadband lower limit (udb1). It is a type-dependent parameter.
udb2 PU Voltage deadband upper limit (udb2). It is a type-dependent parameter.
umax PU Maximum voltage in voltage PI controller integral term (umax) (> WindContQIEC.umin). It is a type-dependent parameter.
umin PU Minimum voltage in voltage PI controller integral term (umin) (< WindContQIEC.umax). It is a type-dependent parameter.
uqdip PU Voltage threshold for UVRT detection in Q control (uqdip). It is a type-dependent parameter.
uref0 PU User-defined bias in voltage reference (uref0). It is a case-dependent parameter.
windQcontrolModesType WindQcontrolModeKind Types of general wind turbine Q control modes (MqG). It is a project-dependent parameter.
windUVRTQcontrolModesType WindUVRTQcontrolModeKind Types of UVRT Q control modes (MqUVRT). It is a project-dependent parameter.
xdroop PU Inductive component of voltage drop impedance (xdroop) (>= 0). It is a project-dependent parameter.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

Source Class Cardinality Source Target Class Cardinality Target Source Name Source Assoc. Description Target Name Target Assoc. Description
WindContQIEC 1 WindTurbineType3or4IEC 1 WIndContQIEC Wind control Q model associated with this wind turbine type 3 or type 4 model. WindTurbineType3or4IEC Wind turbine type 3 or type 4 model with which this reactive control model is associated.