Class Description
Q control model.
Reference: IEC 61400-27-1:2015, 5.6.5.7.
Attributes
Name | Type | Description |
---|---|---|
iqh1 | PU | Maximum reactive current injection during dip (iqh1). It is a type-dependent parameter. |
iqmax | PU | Maximum reactive current injection (iqmax) (> WindContQIEC.iqmin). It is a type-dependent parameter. |
iqmin | PU | Minimum reactive current injection (iqmin) (< WindContQIEC.iqmax). It is a type-dependent parameter. |
iqpost | PU | Post fault reactive current injection (iqpost). It is a project-dependent parameter. |
kiq | PU | Reactive power PI controller integration gain (KI,q). It is a type-dependent parameter. |
kiu | PU | Voltage PI controller integration gain (KI,u). It is a type-dependent parameter. |
kpq | PU | Reactive power PI controller proportional gain (KP,q). It is a type-dependent parameter. |
kpu | PU | Voltage PI controller proportional gain (KP,u). It is a type-dependent parameter. |
kqv | PU | Voltage scaling factor for UVRT current (Kqv). It is a project-dependent parameter. |
rdroop | PU | Resistive component of voltage drop impedance (rdroop) (>= 0). It is a project-dependent parameter. |
tpfiltq | Seconds | Power measurement filter time constant (Tpfiltq) (>= 0). It is a type-dependent parameter. |
tpost | Seconds | Length of time period where post fault reactive power is injected (Tpost) (>= 0). It is a project-dependent parameter. |
tqord | Seconds | Time constant in reactive power order lag (Tqord) (>= 0). It is a type-dependent parameter. |
tufiltq | Seconds | Voltage measurement filter time constant (Tufiltq) (>= 0). It is a type-dependent parameter. |
udb1 | PU | Voltage deadband lower limit (udb1). It is a type-dependent parameter. |
udb2 | PU | Voltage deadband upper limit (udb2). It is a type-dependent parameter. |
umax | PU | Maximum voltage in voltage PI controller integral term (umax) (> WindContQIEC.umin). It is a type-dependent parameter. |
umin | PU | Minimum voltage in voltage PI controller integral term (umin) (< WindContQIEC.umax). It is a type-dependent parameter. |
uqdip | PU | Voltage threshold for UVRT detection in Q control (uqdip). It is a type-dependent parameter. |
uref0 | PU | User-defined bias in voltage reference (uref0). It is a case-dependent parameter. |
windQcontrolModesType | WindQcontrolModeKind | Types of general wind turbine Q control modes (MqG). It is a project-dependent parameter. |
windUVRTQcontrolModesType | WindUVRTQcontrolModeKind | Types of UVRT Q control modes (MqUVRT). It is a project-dependent parameter. |
xdroop | PU | Inductive component of voltage drop impedance (xdroop) (>= 0). It is a project-dependent parameter. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
Source Class | Cardinality Source | Target Class | Cardinality Target | Source Name | Source Assoc. Description | Target Name | Target Assoc. Description |
---|---|---|---|---|---|---|---|
WindContQIEC | 1 | WindTurbineType3or4IEC | 1 | WIndContQIEC | Wind control Q model associated with this wind turbine type 3 or type 4 model. | WindTurbineType3or4IEC | Wind turbine type 3 or type 4 model with which this reactive control model is associated. |