Class Description

Open-circuit test results verify winding turn ratios and phase shifts. They include induced voltage and phase shift measurements on open-circuit windings, with voltage applied to the energised end. For three-phase windings, the excitation can be a positive sequence (the default) or a zero sequence.

Attributes

Name Type Description
energisedEndStep Integer Tap step number for the energised end of the test pair.
energisedEndVoltage Voltage Voltage applied to the winding (end) during test.
openEndStep Integer Tap step number for the open end of the test pair.
openEndVoltage Voltage Voltage measured at the open-circuited end, with the energised end set to rated voltage and all other ends open.
phaseShift AngleDegrees Phase shift measured at the open end with the energised end set to rated voltage and all other ends open.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

Source Class Cardinality Source Target Class Cardinality Target Source Name Source Assoc. Description Target Name Target Assoc. Description
OpenCircuitTest 0..* TransformerEndInfo 1 EnergisedEndOpenCircuitTests All open-circuit test measurements in which this transformer end was excited. EnergisedEnd Transformer end that current is applied to in this open-circuit test.
OpenCircuitTest 0..* TransformerEndInfo 1 OpenEndOpenCircuitTests All open-circuit test measurements in which this transformer end was not excited. OpenEnd Transformer end measured for induced voltage and angle in this open-circuit test.