Class Description
No-load test results determine core admittance parameters. They include exciting current and core loss measurements from applying voltage to one winding. The excitation may be positive sequence or zero sequence. The test may be repeated at different voltages to measure saturation.
Attributes
Name | Type | Description |
---|---|---|
energisedEndVoltage | Voltage | Voltage applied to the winding (end) during test. |
excitingCurrent | PerCent | Exciting current measured from a positive-sequence or single-phase excitation test. |
excitingCurrentZero | PerCent | Exciting current measured from a zero-sequence open-circuit excitation test. |
loss | KiloActivePower | Losses measured from a positive-sequence or single-phase excitation test. |
lossZero | KiloActivePower | Losses measured from a zero-sequence excitation test. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
Source Class | Cardinality Source | Target Class | Cardinality Target | Source Name | Source Assoc. Description | Target Name | Target Assoc. Description |
---|---|---|---|---|---|---|---|
NoLoadTest | 0..* | TransformerEndInfo | 0..1 | EnergisedEndNoLoadTests | All no-load test measurements in which this transformer end was energised. | EnergisedEnd | Transformer end that current is applied to in this no-load test. |