Class Description

Sequence impedance and admittance parameters per unit length, for transposed lines of 1, 2, or 3 phases. For 1-phase lines, define x=x0=xself. For 2-phase lines, define x=xs-xm and x0=xs+xm.

Attributes

Name Type Description
b0ch SusceptancePerLength Zero sequence shunt (charging) susceptance, per unit of length.
bch SusceptancePerLength Positive sequence shunt (charging) susceptance, per unit of length.
g0ch ConductancePerLength Zero sequence shunt (charging) conductance, per unit of length.
gch ConductancePerLength Positive sequence shunt (charging) conductance, per unit of length.
r ResistancePerLength Positive sequence series resistance, per unit of length.
r0 ResistancePerLength Zero sequence series resistance, per unit of length.
x ReactancePerLength Positive sequence series reactance, per unit of length.
x0 ReactancePerLength Zero sequence series reactance, per unit of length.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None