Class Description
Type UEL2 underexcitation limiter which has either a straight-line or multi-segment characteristic when plotted in terms of machine reactive power output vs. real power output.
Reference: IEEE UEL2 421.5-2005, 10.2 (limit characteristic lookup table shown in Figure 10.4 (p 32)).
Attributes
Name | Type | Description |
---|---|---|
q6 | PU | Reactive power values for endpoints (Q6). |
q7 | PU | Reactive power values for endpoints (Q7). |
q8 | PU | Reactive power values for endpoints (Q8). |
q9 | PU | Reactive power values for endpoints (Q9). |
tu1 | Seconds | UEL lead time constant (TU1) (>= 0). Typical value = 0. |
tu2 | Seconds | UEL lag time constant (TU2) (>= 0). Typical value = 0. |
tu3 | Seconds | UEL lead time constant (TU3) (>= 0). Typical value = 0. |
tu4 | Seconds | UEL lag time constant (TU4) (>= 0). Typical value = 0. |
tul | Seconds | Time constant associated with optional integrator feedback input signal to UEL (TUL) (>= 0). Typical value = 0. |
tup | Seconds | Real power filter time constant (TUP) (>= 0). Typical value = 5. |
tuq | Seconds | Reactive power filter time constant (TUQ) (>= 0). Typical value = 0. |
tuv | Seconds | Voltage filter time constant (TUV) (>= 0). Typical value = 5. |
vuimax | PU | UEL integrator output maximum limit (VUIMAX) (> UnderexcLimIEEE2.vuimin). Typical value = 0,25. |
vuimin | PU | UEL integrator output minimum limit (VUIMIN) (< UnderexcLimIEEE2.vuimax). Typical value = 0. |
vulmax | PU | UEL output maximum limit (VULMAX) (> UnderexcLimIEEE2.vulmin). Typical value = 0,25. |
vulmin | PU | UEL output minimum limit (VULMIN) (< UnderexcLimIEEE2.vulmax). Typical value = 0. |
k1 | Float | UEL terminal voltage exponent applied to real power input to UEL limit look-up table (k1). Typical value = 2. |
k2 | Float | UEL terminal voltage exponent applied to reactive power output from UEL limit look-up table (k2). Typical value = 2. |
kfb | PU | Gain associated with optional integrator feedback input signal to UEL (KFB). Typical value = 0. |
kuf | PU | UEL excitation system stabilizer gain (KUF). Typical value = 0. |
kui | PU | UEL integral gain (KUI). Typical value = 0,5. |
kul | PU | UEL proportional gain (KUL). Typical value = 0,8. |
p0 | PU | Real power values for endpoints (P0). Typical value = 0. |
p1 | PU | Real power values for endpoints (P1). Typical value = 0,3. |
p10 | PU | Real power values for endpoints (P10). |
p2 | PU | Real power values for endpoints (P2). Typical value = 0,6. |
p3 | PU | Real power values for endpoints (P3). Typical value = 0,9. |
p4 | PU | Real power values for endpoints (P4). Typical value = 1,02. |
p5 | PU | Real power values for endpoints (P5). |
p6 | PU | Real power values for endpoints (P6). |
p7 | PU | Real power values for endpoints (P7). |
p8 | PU | Real power values for endpoints (P8). |
p9 | PU | Real power values for endpoints (P9). |
q0 | PU | Reactive power values for endpoints (Q0). Typical value = -0,31. |
q1 | PU | Reactive power values for endpoints (Q1). Typical value = -0,31. |
q10 | PU | Reactive power values for endpoints (Q10). |
q2 | PU | Reactive power values for endpoints (Q2). Typical value = -0,28. |
q3 | PU | Reactive power values for endpoints (Q3). Typical value = -0,21. |
q4 | PU | Reactive power values for endpoints (Q4). Typical value = 0. |
q5 | PU | Reactive power values for endpoints (Q5). |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None