Class Description

Simplified type UEL2 underexcitation limiter. This model can be derived from UnderexcLimIEEE2. The limit characteristic (look –up table) is a single straight-line, the same as UnderexcLimIEEE2 (see Figure 10.4 (p 32), IEEE 421.5-2005 Section 10.2).

Attributes

Name Type Description
kui PU Gain Under excitation limiter (KUI). Typical value = 0,1.
p0 PU Segment P initial point (P0). Typical value = 0.
p1 PU Segment P end point (P1). Typical value = 1.
q0 PU Segment Q initial point (Q0). Typical value = -0,31.
q1 PU Segment Q end point (Q1). Typical value = -0,1.
vuimax PU Maximum error signal (VUIMAX) (> UnderexcLim2Simplified.vuimin). Typical value = 1.
vuimin PU Minimum error signal (VUIMIN) (< UnderexcLim2Simplified.vuimax). Typical value = 0.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None