Class Description

Turbine load controller model developed by WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset ‘outer loop’ controllers managing the action of the turbine governor.

Attributes

Name Type Description
pbf Boolean Power controller flag (Pbf).
true = enable load controller
false = disable load controller.
Typical value = false.
pmwset ActivePower Power controller setpoint (Pmwset) (see parameter detail 1). Unit = MW. Typical value = 0.
speedReferenceGovernor Boolean Type of turbine governor reference (Type).
true = speed reference governor
false = load reference governor.
Typical value = true.
tpelec Seconds Power transducer time constant (Tpelec) (>= 0). Typical value = 0.
db PU Controller deadband (db). Typical value = 0.
emax PU Maximum control error (Emax) (see parameter detail 4). Typical value = 0,02.
fb PU Frequency bias gain (Fb). Typical value = 0.
fbf Boolean Frequency bias flag (Fbf).
true = enable frequency bias
false = disable frequency bias.
Typical value = false.
irmax PU Maximum turbine speed/load reference bias (Irmax) (see parameter detail 3). Typical value = 0.
ki PU Integral gain (Ki). Typical value = 0.
kp PU Proportional gain (Kp). Typical value = 0.
mwbase ActivePower Base for power values (MWbase) (> 0). Unit = MW.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None