Class Description
Simplified boiler and steam turbine with PID governor.
Attributes
Name | Type | Description |
---|---|---|
chc | Float | Control valves rate closing limit (Chc). Unit = PU / s. Typical value = -3,3. |
cho | Float | Control valves rate opening limit (Cho). Unit = PU / s. Typical value = 0,17. |
cic | PU | Intercept valves rate closing limit (Cic). Typical value = -2,2. |
cio | PU | Intercept valves rate opening limit (Cio). Typical value = 0,123. |
db1 | PU | Deadband of the frequency corrector (db1). Typical value = 0. |
db2 | PU | Deadband of the speed governor (db2). Typical value = 0,0004. |
hhpmax | PU | Maximum control valve position (Hhpmax). Typical value = 1. |
ke | PU | Gain of the power controller (Ke). Typical value = 0,65. |
kfcor | PU | Gain of the frequency corrector (Kfcor). Typical value = 20. |
khp | PU | Fraction of total turbine output generated by HP part (Khp). Typical value = 0,277. |
klp | PU | Fraction of total turbine output generated by HP part (Klp). Typical value = 0,723. |
komegacor | PU | Gain of the speed governor (Kwcor). Typical value = 20. |
mwbase | ActivePower | Base for power values (MWbase) (> 0). Unit = MW. |
pmax | PU | Maximal active power of the turbine (Pmax). Typical value = 1. |
prhmax | PU | Maximum low pressure limit (Prhmax). Typical value = 1,4. |
simx | PU | Intercept valves transfer limit (Simx). Typical value = 0,425. |
tb | Seconds | Boiler time constant (Tb) (>= 0). Typical value = 100. |
tdp | Seconds | Derivative time constant of the power controller (Tdp) (>= 0). Typical value = 0. |
ten | Seconds | Electro hydraulic transducer (Ten) (>= 0). Typical value = 0,1. |
tf | Seconds | Frequency transducer time constant (Tf) (>= 0). Typical value = 0. |
tfp | Seconds | Time constant of the power controller (Tfp) (>= 0). Typical value = 0. |
thp | Seconds | High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,31. |
tip | Seconds | Integral time constant of the power controller (Tip) (>= 0). Typical value = 2. |
tlp | Seconds | Low pressure (LP) time constant of the turbine (Tlp) (>= 0). Typical value = 0,45. |
tp | Seconds | Power transducer time constant (Tp) (>= 0). Typical value = 0,07. |
trh | Seconds | Reheater time constant of the turbine (Trh) (>= 0). Typical value = 8. |
tvhp | Seconds | Control valves servo time constant (Tvhp) (>= 0). Typical value = 0,1. |
tvip | Seconds | Intercept valves servo time constant (Tvip) (>= 0). Typical value = 0,15. |
tw | Seconds | Speed transducer time constant (Tw) (>= 0). Typical value = 0,02. |
wfmax | PU | Upper limit for frequency correction (Wfmax) (> GovSteamEU.wfmin). Typical value = 0,05. |
wfmin | PU | Lower limit for frequency correction (Wfmin) (< GovSteamEU.wfmax). Typical value = -0,05. |
wmax1 | PU | Emergency speed control lower limit (wmax1). Typical value = 1,025. |
wmax2 | PU | Emergency speed control upper limit (wmax2). Typical value = 1,05. |
wwmax | PU | Upper limit for the speed governor (Wwmax) (> GovSteamEU.wwmin). Typical value = 0,1. |
wwmin | PU | Lower limit for the speed governor frequency correction (Wwmin) (< GovSteamEU.wwmax). Typical value = -1. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None