Class Description
Steam turbine governor, based on the GovSteamIEEE1 (with optional deadband and nonlinear valve gain added).
Attributes
Name | Type | Description |
---|---|---|
db1 | Frequency | Intentional deadband width (db1). Unit = Hz. Typical value = 0. |
db2 | ActivePower | Unintentional deadband (db2). Unit = MW. Typical value = 0. |
eps | Frequency | Intentional db hysteresis (eps). Unit = Hz. Typical value = 0. |
gv1 | PU | Nonlinear gain valve position point 1 (GV1). Typical value = 0. |
gv2 | PU | Nonlinear gain valve position point 2 (GV2). Typical value = 0,4. |
gv3 | PU | Nonlinear gain valve position point 3 (GV3). Typical value = 0,5. |
gv4 | PU | Nonlinear gain valve position point 4 (GV4). Typical value = 0,6. |
gv5 | PU | Nonlinear gain valve position point 5 (GV5). Typical value = 1. |
gv6 | PU | Nonlinear gain valve position point 6 (GV6). Typical value = 0. |
k | PU | Governor gain (reciprocal of droop) (K) (> 0). Typical value = 25. |
k1 | Float | Fraction of HP shaft power after first boiler pass (K1). Typical value = 0,2. |
k2 | Float | Fraction of LP shaft power after first boiler pass (K2). Typical value = 0. |
k3 | Float | Fraction of HP shaft power after second boiler pass (K3). Typical value = 0,3. |
k4 | Float | Fraction of LP shaft power after second boiler pass (K4). Typical value = 0. |
k5 | Float | Fraction of HP shaft power after third boiler pass (K5). Typical value = 0,5. |
k6 | Float | Fraction of LP shaft power after third boiler pass (K6). Typical value = 0. |
k7 | Float | Fraction of HP shaft power after fourth boiler pass (K7). Typical value = 0. |
k8 | Float | Fraction of LP shaft power after fourth boiler pass (K8). Typical value = 0. |
mwbase | ActivePower | Base for power values (MWbase) (> 0). Unit = MW. |
pgv1 | PU | Nonlinear gain power value point 1 (Pgv1). Typical value = 0. |
pgv2 | PU | Nonlinear gain power value point 2 (Pgv2). Typical value = 0,75. |
pgv3 | PU | Nonlinear gain power value point 3 (Pgv3). Typical value = 0,91. |
pgv4 | PU | Nonlinear gain power value point 4 (Pgv4). Typical value = 0,98. |
pgv5 | PU | Nonlinear gain power value point 5 (Pgv5). Typical value = 1. |
pgv6 | PU | Nonlinear gain power value point 6 (Pgv6). Typical value = 0. |
pmax | PU | Maximum valve opening (Pmax) (> GovSteam1.pmin). Typical value = 1. |
pmin | PU | Minimum valve opening (Pmin) (>= 0 and < GovSteam1.pmax). Typical value = 0. |
sdb1 | Boolean | Intentional deadband indicator. |
true = intentional deadband is applied | ||
false = intentional deadband is not applied. | ||
Typical value = true. | ||
sdb2 | Boolean | Unintentional deadband location. |
true = intentional deadband is applied before point “A” | ||
false = intentional deadband is applied after point “A”. | ||
Typical value = true. | ||
t1 | Seconds | Governor lag time constant (T1) (>= 0). Typical value = 0. |
t2 | Seconds | Governor lead time constant (T2) (>= 0). Typical value = 0. |
t3 | Seconds | Valve positioner time constant (T3) (> 0). Typical value = 0,1. |
t4 | Seconds | Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,3. |
t5 | Seconds | Time constant of second boiler pass (T5) (>= 0). Typical value = 5. |
t6 | Seconds | Time constant of third boiler pass (T6) (>= 0). Typical value = 0,5. |
t7 | Seconds | Time constant of fourth boiler pass (T7) (>= 0). Typical value = 0. |
uc | Float | Maximum valve closing velocity (Uc) (< 0). Unit = PU / s. Typical value = -10. |
uo | Float | Maximum valve opening velocity (Uo) (> 0). Unit = PU / s. Typical value = 1. |
valve | Boolean | Nonlinear valve characteristic. |
true = nonlinear valve characteristic is used | ||
false = nonlinear valve characteristic is not used. | ||
Typical value = true. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None