Name | Type | Description |
---|---|---|
tw | Seconds | Water inertia time constant (Tw) (> 0). Typical value = 1. |
velcl | Float | Maximum gate closing velocity (Velcl). Unit = PU / s. Typical value = -0,2. |
velop | Float | Maximum gate opening velocity (Velop). Unit = PU / s. Typical value = 0,2. |
dturb | PU | Turbine damping factor (Dturb). Typical value = 0,2. |
eps | Frequency | Intentional db hysteresis (eps). Unit = Hz. Typical value = 0. |
gmax | PU | Maximum governor output (Gmax) (> GovHydroR.gmin). Typical value = 1,05. |
gmin | PU | Minimum governor output (Gmin) (< GovHydroR.gmax). Typical value = -0,05. |
gv1 | PU | Nonlinear gain point 1, PU gv (Gv1). Typical value = 0. |
gv2 | PU | Nonlinear gain point 2, PU gv (Gv2). Typical value = 0. |
gv3 | PU | Nonlinear gain point 3, PU gv (Gv3). Typical value = 0. |
gv4 | PU | Nonlinear gain point 4, PU gv (Gv4). Typical value = 0. |
gv5 | PU | Nonlinear gain point 5, PU gv (Gv5). Typical value = 0. |
gv6 | PU | Nonlinear gain point 6, PU gv (Gv6). Typical value = 0. |
h0 | PU | Turbine nominal head (H0). Typical value = 1. |
inputSignal | Boolean | Input signal switch (Flag). |
true = Pe input is used | ||
false = feedback is received from CV. | ||
Flag is normally dependent on Tt. If Tt is zero, Flag is set to false. If Tt is not zero, Flag is set to true. | ||
Typical value = true. | ||
kg | PU | Gate servo gain (Kg). Typical value = 2. |
ki | PU | Integral gain (Ki). Typical value = 0,5. |
mwbase | ActivePower | Base for power values (MWbase) (> 0). Unit = MW. |
pgv1 | PU | Nonlinear gain point 1, PU power (Pgv1). Typical value = 0. |
pgv2 | PU | Nonlinear gain point 2, PU power (Pgv2). Typical value = 0. |
pgv3 | PU | Nonlinear gain point 3, PU power (Pgv3). Typical value = 0. |
pgv4 | PU | Nonlinear gain point 4, PU power (Pgv4). Typical value = 0. |
pgv5 | PU | Nonlinear gain point 5, PU power (Pgv5). Typical value = 0. |
pgv6 | PU | Nonlinear gain point 6, PU power (Pgv6). Typical value = 0. |
pmax | PU | Maximum gate opening, PU of MWbase (Pmax) (> GovHydroR.pmin). Typical value = 1. |
pmin | PU | Minimum gate opening, PU of MWbase (Pmin) (< GovHydroR.pmax). Typical value = 0. |
qnl | PU | No-load turbine flow at nominal head (Qnl). Typical value = 0,08. |
r | PU | Steady-state droop (R). Typical value = 0,05. |
t1 | Seconds | Lead time constant 1 (T1) (>= 0). Typical value = 1,5. |
t2 | Seconds | Lag time constant 1 (T2) (>= 0). Typical value = 0,1. |
t3 | Seconds | Lead time constant 2 (T3) (>= 0). Typical value = 1,5. |
t4 | Seconds | Lag time constant 2 (T4) (>= 0). Typical value = 0,1. |
t5 | Seconds | Lead time constant 3 (T5) (>= 0). Typical value = 0. |
t6 | Seconds | Lag time constant 3 (T6) (>= 0). Typical value = 0,05. |
t7 | Seconds | Lead time constant 4 (T7) (>= 0). Typical value = 0. |
t8 | Seconds | Lag time constant 4 (T8) (>= 0). Typical value = 0,05. |
td | Seconds | Input filter time constant (Td) (>= 0). Typical value = 0,05. |
tp | Seconds | Gate servo time constant (Tp) (>= 0). Typical value = 0,05. |
tt | Seconds | Power feedback time constant (Tt) (>= 0). Typical value = 0. |
at | PU | Turbine gain (At). Typical value = 1,2. |
db1 | Frequency | Intentional dead-band width (db1). Unit = Hz. Typical value = 0. |
db2 | ActivePower | Unintentional dead-band (db2). Unit = MW. Typical value = 0. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None