Class Description
Modified single shaft gas turbine.
Attributes
Name | Type | Description |
---|---|---|
a | Float | Turbine power time constant numerator scale factor (a). Typical value = 0,8. |
b | Float | Turbine power time constant denominator scale factor (b) (>0). Typical value = 1. |
db1 | Frequency | Intentional dead-band width (db1). Unit = Hz. Typical value = 0. |
db2 | ActivePower | Unintentional dead-band (db2). Unit = MW. Typical value = 0. |
eps | Frequency | Intentional db hysteresis (eps). Unit = Hz. Typical value = 0. |
fidle | PU | Fuel flow at zero power output (Fidle). Typical value = 0,18. |
gv1 | PU | Nonlinear gain point 1, PU gv (Gv1). Typical value = 0. |
gv2 | PU | Nonlinear gain point 2,PU gv (Gv2). Typical value = 0. |
gv3 | PU | Nonlinear gain point 3, PU gv (Gv3). Typical value = 0. |
gv4 | PU | Nonlinear gain point 4, PU gv (Gv4). Typical value = 0. |
gv5 | PU | Nonlinear gain point 5, PU gv (Gv5). Typical value = 0. |
gv6 | PU | Nonlinear gain point 6, PU gv (Gv6). Typical value = 0. |
ka | PU | Governor gain (Ka). Typical value = 0. |
kt | PU | Temperature limiter gain (Kt). Typical value = 3. |
lmax | PU | Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1. |
loadinc | PU | Valve position change allowed at fast rate (Loadinc). Typical value = 0,05. |
ltrate | Float | Maximum long term fuel valve opening rate (Ltrate). Typical value = 0,02. |
mwbase | ActivePower | Base for power values (MWbase) (> 0). Unit = MW. |
pgv1 | PU | Nonlinear gain point 1, PU power (Pgv1). Typical value = 0. |
pgv2 | PU | Nonlinear gain point 2, PU power (Pgv2). Typical value = 0. |
pgv3 | PU | Nonlinear gain point 3, PU power (Pgv3). Typical value = 0. |
pgv4 | PU | Nonlinear gain point 4, PU power (Pgv4). Typical value = 0. |
pgv5 | PU | Nonlinear gain point 5, PU power (Pgv5). Typical value = 0. |
pgv6 | PU | Nonlinear gain point 6, PU power (Pgv6). Typical value = 0. |
r | PU | Permanent droop (R) (>0). Typical value = 0,04. |
rmax | Float | Maximum fuel valve opening rate (Rmax). Unit = PU / s. Typical value = 1. |
t1 | Seconds | Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5. |
t2 | Seconds | Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5. |
t3 | Seconds | Turbine exhaust temperature time constant (T3) (>= 0). T3 represents delay in the exhaust temperature and load limiting system. Typical value = 3. |
t4 | Seconds | Governor lead time constant (T4) (>= 0). Typical value = 0. |
t5 | Seconds | Governor lag time constant (T5) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0. |
tltr | Seconds | Valve position averaging time constant (Tltr) (>= 0). Typical value = 10. |
vmax | PU | Maximum turbine power, PU of MWbase (Vmax) (> GovGAST1.vmin). Typical value = 1. |
vmin | PU | Minimum turbine power, PU of MWbase (Vmin) (< GovGAST1.vmax). Typical value = 0. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None