Class Description
IEEE VAR controller type 1 which operates by moving the voltage reference directly.
Reference: IEEE 421.5-2005, 11.3.
Attributes
Name | Type | Description |
---|---|---|
tvarc | Seconds | Var controller time delay (TVARC) (>= 0). Typical value = 5. |
vvar | PU | Synchronous machine power factor (VVAR). |
vvarcbw | Float | Var controller deadband (VVARC_BW). Typical value = 0,02. |
vvarref | PU | Var controller reference (VVARREF). |
vvtmax | PU | Maximum machine terminal voltage needed for pf/VAr controller to be enabled (VVTMAX) (> PVFArType1IEEEVArController.vvtmin). |
vvtmin | PU | Minimum machine terminal voltage needed to enable pf/var controller (VVTMIN) (< PVFArType1IEEEVArController.vvtmax). |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None