Class Description

Field voltage or current overexcitation limiter designed to protect the generator field of an AC machine with automatic excitation control from overheating due to prolonged overexcitation.

Attributes

Name Type Description
efd1 PU Low voltage or current point on the inverse time characteristic (EFD1). Typical value = 1,1.
efd2 PU Mid voltage or current point on the inverse time characteristic (EFD2). Typical value = 1,2.
efd3 PU High voltage or current point on the inverse time characteristic (EFD3). Typical value = 1,5.
efddes PU Desired field voltage if m = false or desired field current if m = true (EFDDES). Typical value = 1.
efdrated PU Rated field voltage if m = false or rated field current if m = true (EFDRATED). Typical value = 1,05.
kmx PU Gain (KMX). Typical value = 0,002.
m Boolean (m).
true = IFD limiting
false = EFD limiting.
t1 Seconds Time to trip the exciter at the low voltage or current point on the inverse time characteristic (TIME1) (>= 0). Typical value = 120.
t2 Seconds Time to trip the exciter at the mid voltage or current point on the inverse time characteristic (TIME2) (>= 0). Typical value = 40.
t3 Seconds Time to trip the exciter at the high voltage or current point on the inverse time characteristic (TIME3) (>= 0). Typical value = 15.
vlow PU Low voltage limit (VLOW) (> 0).

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None