Class Description

Types of connections for the UEL input used for static excitation systems type 7B.

Attributes

Name Type Description
noUELinput No UEL input is used. Corresponds to UELin not = 1 and not = 2 and not = 3 on the ExcST7B diagram. Original ExcST7B model would have called this UELin = 0.
addVref The signal is added to Vref. Corresponds to UELin = 1 on the ExcST7B diagram.
inputHVgate The signal is connected into the input HVGate. Corresponds to UELin = 2 on the ExcST7B diagram.
outputHVgate The signal is connected into the output HVGate. Corresponds to UELin = 3 on the ExcST7B diagram.

Relationships

Inherits from

  • None

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None