Class Description

IEEE 421.5-2005 type AC4A model. The model represents type AC4A alternator-supplied controlled-rectifier excitation system which is quite different from the other types of AC systems. This high initial response excitation system utilizes a full thyristor bridge in the exciter output circuit. The voltage regulator controls the firing of the thyristor bridges. The exciter alternator uses an independent voltage regulator to control its output voltage to a constant value. These effects are not modelled; however, transient loading effects on the exciter alternator are included.
Reference: IEEE 421.5-2005, 6.4.

Attributes

Name Type Description
ka PU Voltage regulator gain (KA) (> 0). Typical value = 200.
kc PU Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0.
ta Seconds Voltage regulator time constant (TA) (> 0). Typical value = 0,015.
tb Seconds Voltage regulator time constant (TB) (>= 0). Typical value = 10.
tc Seconds Voltage regulator time constant (TC) (>= 0). Typical value = 1.
vimax PU Maximum voltage regulator input limit (VIMAX) (> 0). Typical value = 10.
vimin PU Minimum voltage regulator input limit (VIMIN) (< 0). Typical value = -10.
vrmax PU Maximum voltage regulator output (VRMAX) (> 0). Typical value = 5,64.
vrmin PU Minimum voltage regulator output (VRMIN) (< 0). Typical value = -4,53.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None