Class Description
IEEE 421.5-2005 type AC2A model. The model represents a high initial response field-controlled alternator-rectifier excitation system. The alternator main exciter is used with non-controlled rectifiers. The type AC2A model is similar to that of type AC1A except for the inclusion of exciter time constant compensation and exciter field current limiting elements.
Reference: IEEE 421.5-2005, 6.2.
Attributes
Name | Type | Description |
---|---|---|
ka | PU | Voltage regulator gain (KA) (> 0). Typical value = 400. |
kb | PU | Second stage regulator gain (KB) (> 0). Typical value = 25. |
kc | PU | Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0,28. |
kd | PU | Demagnetizing factor, a function of exciter alternator reactances (KD) (>= 0). Typical value = 0,35. |
ke | PU | Exciter constant related to self-excited field (KE) (>= 0). Typical value = 1. |
kf | PU | Excitation control system stabilizer gains (KF) (>= 0). Typical value = 0,03. |
kh | PU | Exciter field current feedback gain (KH) (>= 0). Typical value = 1. |
seve1 | Float | Exciter saturation function value at the corresponding exciter voltage, VE1, back of commutating reactance (SE[VE1]) (>= 0). Typical value = 0,037. |
seve2 | Float | Exciter saturation function value at the corresponding exciter voltage, VE2, back of commutating reactance (SE[VE2]) (>= 0). Typical value = 0,012. |
ta | Seconds | Voltage regulator time constant (TA) (> 0). Typical value = 0,02. |
tb | Seconds | Voltage regulator time constant (TB) (>= 0). Typical value = 0. |
tc | Seconds | Voltage regulator time constant (TC) (>= 0). Typical value = 0. |
te | Seconds | Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,6. |
tf | Seconds | Excitation control system stabilizer time constant (TF) (> 0). Typical value = 1. |
vamax | PU | Maximum voltage regulator output (VAMAX) (> 0). Typical value = 8. |
vamin | PU | Minimum voltage regulator output (VAMIN) (< 0). Typical value = -8. |
ve1 | PU | Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE1) (> 0). Typical value = 4,4. |
ve2 | PU | Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE2) (> 0). Typical value = 3,3. |
vfemax | PU | Exciter field current limit reference (VFEMAX) (> 0). Typical value = 4,4. |
vrmax | PU | Maximum voltage regulator outputs (VRMAX) (> 0). Typical value = 105. |
vrmin | PU | Minimum voltage regulator outputs (VRMIN) (< 0). Typical value = -95. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None