Name | Type | Description |
---|---|---|
a1 | PU | Lead coefficient (A1). Typical value = 0,5. |
a2 | PU | Lag coefficient (A2). Typical value = 0,5. |
a3 | PU | Lead coefficient (A3). Typical value = 0,5. |
a4 | PU | Lag coefficient (A4). Typical value = 0,5. |
a5 | PU | Lead coefficient (A5). Typical value = 0,5. |
a6 | PU | Lag coefficient (A6). Typical value = 0,5. |
k1 | PU | Gain (K1). Typical value = 1. |
k3 | PU | Gain (K3). Typical value = 3. |
k5 | PU | Gain (K5). Typical value = 1. |
t1 | Seconds | Lead time constant (T1) (>= 0). Typical value = 0,05. |
t2 | Seconds | Lag time constant (T2) (>= 0). Typical value = 0,1. |
t3 | Seconds | Lead time constant (T3) (>= 0). Typical value = 0,1. |
t4 | Seconds | Lag time constant (T4) (>= 0). Typical value = 0,1. |
t5 | Seconds | Lead time constant (T5) (>= 0). Typical value = 0,1. |
t6 | Seconds | Lag time constant (T6) (>= 0). Typical value = 0,1. |
vmax1 | PU | Lead-lag maximum limit (Vmax1) (> ExcAVR7.vmin1). Typical value = 5. |
vmax3 | PU | Lead-lag maximum limit (Vmax3) (> ExcAVR7.vmin3). Typical value = 5. |
vmax5 | PU | Lead-lag maximum limit (Vmax5) (> ExcAVR7.vmin5). Typical value = 5. |
vmin1 | PU | Lead-lag minimum limit (Vmin1) (< ExcAVR7.vmax1). Typical value = -5. |
vmin3 | PU | Lead-lag minimum limit (Vmin3) (< ExcAVR7.vmax3). Typical value = -5. |
vmin5 | PU | Lead-lag minimum limit (Vmin5) (< ExcAVR7.vmax5). Typical value = -2. |
Relationships