Class Description

IVO excitation system.

Attributes

Name Type Description
a1 PU Lead coefficient (A1). Typical value = 0,5.
a2 PU Lag coefficient (A2). Typical value = 0,5.
a3 PU Lead coefficient (A3). Typical value = 0,5.
a4 PU Lag coefficient (A4). Typical value = 0,5.
a5 PU Lead coefficient (A5). Typical value = 0,5.
a6 PU Lag coefficient (A6). Typical value = 0,5.
k1 PU Gain (K1). Typical value = 1.
k3 PU Gain (K3). Typical value = 3.
k5 PU Gain (K5). Typical value = 1.
t1 Seconds Lead time constant (T1) (>= 0). Typical value = 0,05.
t2 Seconds Lag time constant (T2) (>= 0). Typical value = 0,1.
t3 Seconds Lead time constant (T3) (>= 0). Typical value = 0,1.
t4 Seconds Lag time constant (T4) (>= 0). Typical value = 0,1.
t5 Seconds Lead time constant (T5) (>= 0). Typical value = 0,1.
t6 Seconds Lag time constant (T6) (>= 0). Typical value = 0,1.
vmax1 PU Lead-lag maximum limit (Vmax1) (> ExcAVR7.vmin1). Typical value = 5.
vmax3 PU Lead-lag maximum limit (Vmax3) (> ExcAVR7.vmin3). Typical value = 5.
vmax5 PU Lead-lag maximum limit (Vmax5) (> ExcAVR7.vmin5). Typical value = 5.
vmin1 PU Lead-lag minimum limit (Vmin1) (< ExcAVR7.vmax1). Typical value = -5.
vmin3 PU Lead-lag minimum limit (Vmin3) (< ExcAVR7.vmax3). Typical value = -5.
vmin5 PU Lead-lag minimum limit (Vmin5) (< ExcAVR7.vmax5). Typical value = -2.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None