Class Description
Modified IEEE AC2A alternator-supplied rectifier excitation system with different field current limit.
Attributes
Name | Type | Description |
---|---|---|
ve2 | PU | Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 3,3. |
vfemax | PU | Exciter field current limit reference (Vfemax) (>= 0). Typical value = 4,4. |
vlr | PU | Maximum exciter field current (Vlr) (> 0). Typical value = 4,4. |
vrmax | PU | Maximum voltage regulator outputs (Vrmax) (> 0). Typical value = 105. |
vrmin | PU | Minimum voltage regulator outputs (Vrmin) (< 0). Typical value = -95. |
hvgate | Boolean | Indicates if HV gate is active (HVgate). |
true = gate is used | ||
false = gate is not used. | ||
Typical value = true. | ||
ka | PU | Voltage regulator gain (Ka) (> 0). Typical value = 400. |
kb | PU | Second stage regulator gain (Kb) (> 0). Exciter field current controller gain. Typical value = 25. |
kb1 | PU | Second stage regulator gain (Kb1). It is exciter field current controller gain used as alternative to Kb to represent a variant of the ExcAC2A model. Typical value = 25. |
kc | PU | Rectifier loading factor proportional to commutating reactance (Kc) (>= 0). Typical value = 0,28. |
kd | PU | Demagnetizing factor, a function of exciter alternator reactances (Kd) (>= 0). Typical value = 0,35. |
ke | PU | Exciter constant related to self-excited field (Ke). Typical value = 1. |
kf | PU | Excitation control system stabilizer gains (Kf) (>= 0). Typical value = 0,03. |
kh | PU | Exciter field current feedback gain (Kh) (>= 0). Typical value = 1. |
kl | PU | Exciter field current limiter gain (Kl). Typical value = 10. |
kl1 | PU | Coefficient to allow different usage of the model (Kl1). Typical value = 1. |
ks | PU | Coefficient to allow different usage of the model-speed coefficient (Ks) (>= 0). Typical value = 0. |
lvgate | Boolean | Indicates if LV gate is active (LVgate). |
true = gate is used | ||
false = gate is not used. | ||
Typical value = true. | ||
seve1 | Float | Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0,037. |
seve2 | Float | Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 0,012. |
ta | Seconds | Voltage regulator time constant (Ta) (> 0). Typical value = 0,02. |
tb | Seconds | Voltage regulator time constant (Tb) (>= 0). Typical value = 0. |
tc | Seconds | Voltage regulator time constant (Tc) (>= 0). Typical value = 0. |
te | Seconds | Exciter time constant, integration rate associated with exciter control (Te) (> 0). Typical value = 0,6. |
tf | Seconds | Excitation control system stabilizer time constant (Tf) (> 0). Typical value = 1. |
vamax | PU | Maximum voltage regulator output (Vamax) (> 0). Typical value = 8. |
vamin | PU | Minimum voltage regulator output (Vamin) (< 0). Typical value = -8. |
ve1 | PU | Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 4,4. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Leaf/Root class
IsLeaf | IsRoot |
---|---|
False | False |
Associations
None