Class Description

This contains the information that a particular actor exposes for a particular agreed upon ICCP Bilateral Table.

Attributes

Name Type Description
supportForBlock2 Boolean Per IEC 60870-6-702: If true indicates support for extended conditions.
supportForBlock3 Boolean Per IEC 60870-6-702: If true indicates support for blocked transfers.
supportForBlock4 Boolean Per IEC 60870-6-702: If true indicates support for information messages.
supportForBlock5 Boolean Per IEC 60870-6-702: If true indicates support for device control.
supportForDepriciatedBlock8 Boolean Per IEC 60870-6-702: If true indicates support for accounts. The use of this block was deprecated in Edition 3.
transportSecurityRequirement Boolean If true, then transport level security as specified by IEC 62351-6 is required.
applicationSecurityRequirement ApplicationSecurityKind Specifies the expected security mechanism, per IEC 62351-4, to be utilized.
calling Boolean Used to indicate if the Provider is responsible for initiating the TASE.2 connection. If the value is TRUE, the provider is responsible for establishing the association. If the value is FALSE, the peer provider of the Bilateral Table will need to establish the association.
clientAndServer Boolean If True the value indicates that the entity represented by the bilateral table is capable of issuing requests and responding to request (e.g. bidirectional support of ICCP requests).
If False, this indicates that a calling entity (e.g. calling = True) will not be able to respond to ICCP requests. If False, and calling=False, this indicates that the entity will only respond to ICCP requests and not issue ICCP requests.
minimumUpdateInterval Integer Specifies the fastest update interval that can be provided for integrity information and Transfer Set creation. The value is in seconds.
nameOfLocalICC String Specifies the ICC scope name that the remote can use to access the information in the Bilateral Table if the information is not VCC scoped. This value may not be null.
supportForBlock1 Boolean Per IEC 60870-6-702: If true indicates support for basic services. Must always be true.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None