Class Description

Properties of surge arrester.

Attributes

Name Type Description
continuousOperatingVoltage Voltage Maximum continuous power frequency voltage allowed on the surge arrester.
isPolymer Boolean If true, the arrester has a polymer housing, porcelain otherwise.
lightningImpulseDischargeVoltage Voltage Residual voltage during an 8x20 microsecond current impulse at the nominal discharge current level.
lineDischargeClass Integer Determines the arrester energy discharge capability. Choices are limited to 0 (none) through 5 (highest) by IEC 60099. Classes 1..3 require a 10-kA nominal discharge current. Classes 4..5 require a 20-kA nominal discharge current. Lower nominal discharge currents must use class 0.
nominalDischargeCurrent CurrentFlow The lightning discharge current used to classify the arrester. Choices are limited to 1.5, 2.5, 5, 10, and 20 kA by IEC 60099.
pressureReliefClass CurrentFlow Fault current level at which all parts of the failed arrester lie within a circle prescribed by IEC 60099.
ratedVoltage Voltage The temporary overvoltage (TOV) level at power frequency that the surge arrester withstands for 10 seconds.
steepFrontDischargeVoltage Voltage Residual voltage during a current impulse with front time of 1 microsecond, and magnitude equal to the nominal discharge current level.
switchingImpulseDischargeVoltage Voltage Residual voltage during a current impulse with front time of at least 30 microseconds, and magnitude specified in IEC 60099 for the line discharge class. Does not apply to line discharge class 0.

Relationships

Inherits from

Descendant classes

  • No descendant classes

Leaf/Root class

IsLeaf IsRoot
False False

Associations

None